APPENDICES
Appendix 2 Dedicated Instruction
Appendix 2.2 G(P).OFFGAN
APPX - 4
APPENDICESINDEX
(1) Function
Switches the mode of the Q68TD-G-H02(H01) converter module
Normal mode to offset/gain setting mode (the offset/gain setting mode status flag
(XA) turns ON)
Offset/gain setting mode to normal mode (the offset/gain setting mode status flag
(XA) turns OFF)
POINT
(1) When the offset/gain setting mode is switched to the normal mode, Module
ready (X0) turns from OFF to ON.
Note that initial setting processing will be executed if there is a sequence
program that makes initial setting when Module ready (X0) turns ON.
(2) When the normal mode is switched to the offset/gain setting mode, all
channels set to temperature conversion disable.
Set the channels where offset/gain setting will be made for conversion enable
and turn ON the operating condition setting request (Y9).
(3) When the offset/gain setting mode is switched to the normal mode, restore
the normal mode status prior to switching to the offset/gain setting mode and
start temperature conversion.
(2) Operation error
No errors.
(3) Program example
The following program is designed to switch the Q68TD-G-H02(H01) converter
module mounted in the position of I/O number X/Y0 to X/YF to the offset/gain setting
mode when M10 is turned ON, and to return it to the normal mode when M10 is turned
OFF.
Figure APPX.2 Program example
Dedicated instruction
(G.OFFGAN)
Dedicated instruction
(G.OFFGAN)
Stores "1: Switching to
offset/gain setting mode".
Stores "0: Switching to
normal mode".
Switching to offset/gain setting mode
Switching to normal mode
Processing of offset/gain mode setting
Processing in normal mode