Mitsubishi Q68TD-G-H01 Thermometer User Manual


 
7
ONLINE MODULE CHANGE
7.3 Online Module Change Procedure
7.3.3 When user range setting is used and initial setting was made with GX Configurator-TI (other system
7 - 13
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
TROUBLESHOOTING
7.3.3 When user range setting is used and initial setting was made with
GX Configurator-TI (other system is available)
(1) Conversion disable
(a) Set conversion enable/disable setting (Un\G0) for all channel conversion disable
and turn Operating Condition Setting Request (Y9) from OFF to ON to stop
conversion.
After confirming that conversion has stopped with the Conversion Completion
Flag (Un\G10), turn off Operating Condition Setting Request (Y9).
Figure 7.22 "Device test" screen
(2) Dismounting of module
(a) After choosing [Diagnosis] - [Online module change] on GX Developer to enter the
"Online module change" mode, double-click the module to be changed online to
display the "Online module change" screen.
Figure 7.23 "System Monitor" screen