Mitsubishi Q68TD-G-H01 Thermometer User Manual


 
3
SPECIFICATIONS
3.4 Buffer Memory
3.4.5 CH[ ] Measured temperature value (Un\G11 to Un\G18)
3 - 41
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
TROUBLESHOOTING
3.4.5 CH[ ] Measured temperature value (Un\G11 to Un\G18)
“Thermal electromotive force values” input from thermocouples are converted into
“temperature values” to check values of detected temperature.
(1) Data storage
The measured temperature value rounded off to one decimal place is multiplied by 10
and the result is stored into buffer memory in 16-bit signed binary. (Drop the second
decimal place and later.)
[Setting example 1]
When the measured temperature value is 123.025 1230 is stored.
Figure 3.23 Storage example 1 of CH Measured temperature value (Un\G11 to Un\G18)
When the measured temperature value is -123.0 -1230 is stored.
Figure 3.24 Storage example 2 of CH Measured temperature value (Un\G11 to Un\G18)
POINT
(1) When disconnection is detected or checked with a monitor, the values set in
Conversion setting for disconnection detection (Un\G164, Un\G165) or
Disconnection state conversion setting (Un\G164, Un\G165) are stored into
the CH Measured temperature value (Un\G11 to Un\G18). (Refer to Section
3.4.25, Section 3.4.26)
(2) After the disconnection recovery, normal measured temperature value is
automatically stored.
(3) Use Conversion completion flag (XE) or Conversion completion flag (Un\G10)
as an interlock to read out the measured temperature value.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
1100111000000100
b12b11b10b9b8b7b6b5b4b3b2b1b0
00110010
b15 b14 b13
11111011