Mitsubishi Q68TD-G-H01 Thermometer User Manual


 
3 - 18
3.2 Function List
3.2.4 Warning output function
3
SPECIFICATIONS
(b) Warning clearance
After a warning occurrence, when the changed portion of the measured
temperature value falls lower than the rate alarm upper limit value or rises higher
than the rate alarm lower limit value, and returns to within the setting range, the
warning is cleared.
When the warning is cleared, "0" is stored in the bit position corresponding to the
channel of the warning output flag (rate alarm)(Un\G48).
The warning output signal (XD) turns OFF and the "ALM" LED turns off only when
the process alarm and rate alarm warings for all channels do not occur or are in
clearance state.
Figure 3.9 Warning output occurence and clearance (Rate alarm)
(c) Set the rate alarm upper limit/lower limit values in units of 0.1 for the measured
temperature range.
Setting range is -32768 to 32767 (-3276.8 to 3276.7 ).
Initial value is set to "0".
CH1 measured
temperature
value
CH2
measured
temperature
value
Time
Time
Rate alarm
upper limit
value
Rate alarm
lower limit
value
Change of
CH1
measured
temperature
value
Change of CH2
measured
temperature value
CH1 Rate alarm upper
limit value (Un\G48.b0)
CH1 Rate alarm lower
limit value (Un\G48.b1)
CH2 Rate alarm upper
limit value (Un\G48.b2)
Warning output signal (XD)
Change of
measured
temperature
value ( C)
Measured
temperature
value
Rate alarm
warning
detection
period
Rate alarm
warning
detection
period