Mitsubishi Q68TD-G-H01 Thermometer User Manual


 
4 - 18
4.7 Cold Junction Temperature Compensation with/without Setting
4
SETUP AND PROCEDURES BEFORE OPERATION
4.7 Cold Junction Temperature Compensation with/without Setting
The Q68TD-G-H02(H01) can execute the following two different cold junction temperature
compensations by setting the inteligent function module switch setting (switch 4) to
whether to carry out the cold junction temperature compensation using the cold junction
temperature compensation resistor (RTD) or not.
(1) Executing cold junction temperature compensation with the cold
junction temperature compensation resistor (RTD) (set to "with cold
junction temperature compensation")
Cold junction temperature compensation is possible by connecting the supplied cold
junction temperature compensation resistor (RTD) and setting it to "with cold junction
temperature compensation".
Always connect the supplied cold junction temperature compensation resistor (RTD)
to the terminal block. (For connection, refer to Section 4.4.2.)
Figure 4.12 Connection between a cold junction compensation resistor (RTD) and a relay terminal block
(2) Executing cold junction temperatuer compensation externally (set to
"without cold junction temperature compensation")
Use this function to measure temperature in higher accuracy than the cold junction
temperature compensation accuracy ( 1 ) by the cold junction temperature
compensation resistor (RTD) that is included with the Q68TD-G-H02 (H01).
Connecting a cold junction temperature compensation resistor (RTD) to the terminal
block is unnecessary.
By providing a precision ice bath externally, the thermoelectromotive force generated
at the tip of the thermocouple can be led to this module without any change, improving
the cold junction temperature compensation accuracy.
Figure 4.13 Connection between an ice bath and a relay terminal block
Thermocouple
Compensation conductor
Object whose temperature
is to be measured
Terminal block
Q68TD-G-H02(H01)
RTD
Compensation conductor
Ice bath
Object whose temperature
is to be measured
Thermocouple
Conductor
Terminal block
Q68TD-G-H02(H01)