7.3.5 When user range setting is used and initial setting was made with
sequence program (other system is available)
(1) Conversion disable
(a) Set conversion enable/disable setting (Un\G0) for all channel conversion disable
and turn Operating Condition Setting Request (Y9) from OFF to ON to stop
conversion.
After confirming that conversion has stopped with the Conversion Completion
Flag (Un\G10), turn off Operating Condition Setting Request (Y9).
Figure 7.45 "Device test" screen
(2) Dismounting of module
(a) After choosing [Diagnosis] - [Online module change] on GX Developer to enter the
"Online module change" mode, double-click the module to be changed online to
display the "Online module change" screen.
]
Figure 7.46 "System Monitor" screen