Mitsubishi Q68TD-G-H01 Thermometer User Manual


 
APPX - 9
Appendix 2 Dedicated Instruction
Appendix 2.4 G(P).OGSTOR
APPENDICES
Appendix 2.4 G(P).OGSTOR
Restores the offset/gain values of the user range setting stored in the CPU to the Q68TD-
G-H02(H01) converter module.
Figure APPX.6 How to write a program
* 1 When executing the G.OGLOAD instruction, specify the device designated in (S).
Do not change the data read with the G.OGLOAD instruction.
If it is changed, normal operation cannot be guaranteed.
Table APPX.10 Available device List
Set data
Usable devices
Internal device
(System, user)
File
register
Link direct device
J\
Intelligent
function
module
U\G
Index
register
Z
Constant
Other
Bit Word Bit Word K, H $
(S) - - - - -
(D) - - - -
Table APPX.11 Set data list
Set data Description Setting range Data type
Un Start I/O number of the module 0 to FEH Binary 16 bits
(S)
*1
Start number of the device in which control data is stored.
Within the range of the
specified device
Device name
(D)
Device that is turned ON 1 scan on completion of dedicated
instruction processing.
(D) + 1 also turns ON at an abnormal completion.
Within the range of the
specified device
Bit
G.OGSTOR
[Instruction
symbol]
[Execution
condition]
G.OGSTOR
GP.OGSTOR
Command
Command
G.OGSTOR Un (S)
(D)
GP.OGSTOR
Un
(S) (D)