3 - 42
3.4 Buffer Memory
3.4.6 Error code (Un\G19)
3
SPECIFICATIONS
3.4.6 Error code (Un\G19)
Error codes that are detected by the Q68TD-G-H02(H01) are stored. (Refer to Section
8.1)
3.4.7 Setting range 1, 2 (Thermocouple type) (Un\G20,Un\G21)
This area is for checking thermocouple type of the Q68TD-G-H02(H01). which is set with
Switch 1 and 2 in the intelligent function module switch setting. (Refer to Section 4.5)
(1) Data storage
(a) The setting value of thermocouple type is stored into the position shown in the
following figure for each channel.
Figure 3.25 Storage of setting range 1,2 (thermocouple type) (Un\G20,Un\G21)
(b) The following table shows the setting value for each thermocouple type.
3.4.8 Setting range 3 (Offset/gain setting) (Un\G22)
This area is for checking offset/gain setting of the Q68TD-G-H02(H01). which is set with
Switch 3 in the intelligent function module switch setting. (Refer to Section 4.5)
(1) Data storage
The setting value of offset/gain setting is stored into the position corresponding to the
channels shown in the following figure.
Figure 3.26 Storage of setting range 3 (Offset/gain setting) (Un\G22)
Table 3.11 Thermocouple and setting value
Themocouple type Setting value
Thermocouple K 0H
Thermocouple E 1H
Thermocouple J 2H
Thermocouple T 3H
Thermocouple B 4H
Thermocouple R 5H
Thermocouple S 6H
Thermocouple N 7H
b0
Un\G20
(Setting range CH1 to CH4)
Un\G21
(Setting range CH5 to CH8)
b15
b12 b11
b8 b7
b4b3
CH4 CH3 CH1
CH8 CH7 CH6 CH5
CH2
to
to
to
to
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
CH8 CH7 CH6 CH5 CH4 CH3 CH2 CH100000000
Data for b8 to b15 are fixed to "0".
0: Factory default setting
1: User range setting