Mitsubishi Q68TD-G-H01 Thermometer User Manual


 
7
ONLINE MODULE CHANGE
7.3 Online Module Change Procedure
7.3.6 When user range setting is used and initial setting was made with sequence program (other system
7 - 31
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
TROUBLESHOOTING
(4) Operation check
(a) To make an operation check, click the button to cancel control
resumption.
Figure 7.60 Cancel of control resumption
(b) Click the button to leave the "Online module change" mode.
Figure 7.61 "Online module change" mode stop
(c) Click the button to close the System monitor screen.
Figure 7.62 "System Monitor" screen
(d) Choose [Online] - [Debug] - [Device test] on GX Developer and set the values
prerecorded in Section 7.3.6 (2) to the buffer memory.
(e) Turn the user range write request (YA) from OFF to ON to restore the user set
values to the module.
After confirming that the offset/gain setting mode status flag (XA) is ON, turn OFF
the user range write request (YA).