3 - 4
3.1 Performance Specifications
3
SPECIFICATIONS
* 1 If a value entered from the thermocouple is outside the measured temperature range given in the
table, it is handled as the maximum/minimum value of the measured temperature range.
* 2 The accuracies only in the temperature ranges of Class 1 to 3 (shaded areas) in JIS C1602-1995
apply.
Also, a warm-up (power distribution) period of 30 minutes is required to satisfy with the accuracy.
* 3 Temperature measurement can be executed, but accuracy is not guaranteed.
* 4 This is the temperature error per 1Ω wiring resistance of the thermocouple. The temperature error
can be corrected by the offset/gain setting. (Refer to Section 4.6.)
T
-270 to -200
------
*3
------
*3
------
*3
------
*3
-200 to 0
*2
Larger value of 0.5 and
0.5% of measured
temperature
Larger value of 0.06 and
0.1% of measured
temperature
6.0
-0.036 /Ω
-0.009 /Ω
0 to 350
*2
Larger value of 0.5 and
0.25% of measured
temperature
Larger value of 0.06 and
0.02% of measured
temperature
2.625
-0.026 /Ω
-0.007 /Ω
350 to 400
------
*3
------
*3
------
*3
------
*3
N
-270 to -200
------
*3
------
*3
------
*3
------
*3
-200 to 0
*2
Larger value of 0.5 and
0.5% of measured
temperature
Larger value of 0.06 and
0.2% of measured
temperature
11.0
-0.048 /Ω
-0.012 /Ω
0 to 1250
*2
Larger value of 0.5 and
0.25% of measured
temperature
Larger value of 0.06 and
0.02% of measured
temperature
9.375
-0.039 /Ω
-0.010 /Ω
1250 to 1300
------
*3
------
*3
------
*3
------
*3
Table 3.2 Applicable thermocouples, conversion accuracy, and the effect from wiring resistance of 1Ω