Mitsubishi Q68TD-G-H01 Thermometer User Manual


 
3
SPECIFICATIONS
3.2 Function List
3.2.3 Disconnection state conversion setting function (Q68TD-G-H01 only)
3 - 15
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
TROUBLESHOOTING
(2) Setting methods
When “Up scale”, “Down scale” or “Given value” is selected in Disconnection state
conversion setting (Un\G164,Un\G165), the value to be stored into the CH
Measured temperature value (Un\G11 to Un\G18) in disconnection check can be
specified.
(a) Up-scale and down-scale
When “Up scale” (0H) or “Down scale” (1H) is selected, an up-scale value or
down-scale value of thermocouple-type to be used is stored into the CH
Measured temperature value (Un\G11 to Un\G18).
(b) Given value
When “Given value” (2H) is selected, set a value in the CH CH1 Conversion
setting value for disconnection state (Un\G166 to Un\G173) in units of 0.1 .
The value set in the buffer memory above is stored in the CH Measured
temperature value (Un\G11 to Un\G18) during disconnection state.
Table 3.5 Up-scale and down-scale list
Thermocouple
type
Setting value
Measurement
range
Measured temperature value when
disconnection is detected
Up scale Down scale
Thermocouple K 0
-270 to 1370 1452.0 -352.0
Thermocouple E 1
-270 to 1000 1063.5 -333.5
Thermocouple J 2
-210 to 1200 1270.5 -280.5
Thermocouple T 3
-270 to 400 433.5 -303.5
Thermocouple B 4
0 to 1820 1911.0 -91.0
Thermocouple R 5
-50 to 1760 1850.5 -140.5
Thermocouple S 6
-50 to 1760 1850.5 -140.5
Thermocouple N 7
-270 to 1300 1378.5 -348.5