Mitsubishi Q68TD-G-H01 Thermometer User Manual


 
6
PROGRAMMING
6.3 Using Programs on Remote I/O Network
6 - 16
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
TROUBLESHOOTING
(3) Programming conditions
(a) Use the following temperature conversion system for each channel
CH1: Sampling processing
CH2: Count average (5 times)
CH3: Primary delay filter (Time constant 960ms)
(b) Use the following function at each channel.
CH2: Warning output function
CH3: Warning output function
(c) Use the following setting for Conversion setting for disconnection detection of
CH1 to CH3.
CH1 to CH3: Down scale (-352.0 )[Default setting]
(d) When a write error occurs, the corresponding error code is output to an output
module in BCD value.
Process alarm lower lower limit value: 2000 (200 )
Process alarm lower upper limit value: 2050 (205 )
Process alarm upper lower limit value: 2950 (295 )
Process alarm upper upper limit value: 3000 (300 )
Rate alarm warning detection period: 3 times (960ms),
Rate alarm upper limit value: 50 (+ 5.0 )
Rate alarm lower limit value: - 50 (- 5.0 )