7.3 Online Module Change Procedure
7.3.5 When user range setting is used and initial setting was made with sequence program (other system
7 - 25
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
TROUBLESHOOTING
(3) Mounting of new module
(a) Mount the dismounted module and new module to the other system.
(b) Using the G(P).OGLOAD instruction, save the user range setting values to the
CPU device. Refer to Appendix 2.3 for the G(P).OGLOAD instruction.
(c) Using the G(P).OGSTOR instruction, restore the user range setting set values to
the module. Refer to Appendix 2.4 for the G(P).OGSTOR instruction.
(d) Dismount a new module from the other system, mount it to the slot from where the
old module was dismounted in the original system, and install the connector.
(e) After mounting the module, click the button and make sure that the
"RUN" LED is lit. Module ready (X0) remains OFF.
Figure 7.49 "Online module change" screen
(4) Operation check
(a) To make an operation check, click the button to cancel control
resumption.
Figure 7.50 Cancel of control resumption