Emerson 00809-0100-4102 Sleep Apnea Machine User Manual


 
86
Reference Manual
00809-0100-4102, Rev AA
Section 6: Troubleshooting
May 2013
Troubleshooting
LO Alarm The primary variable has surpassed
the user defined limit.
1. Verify that the process variable is within user
specified limits
2. Reconfirm the user defined alarm limit
3. If not needed, disable this alert
LO LO Alarm The primary variable has surpassed
the user defined limit.
1. Verify that the process variable is within user
specified limits
2. Reconfirm the user defined alarm limit
3. If not needed, disable this alert
Button Stuck A buttons on the Electronics Board
is detected as stuck in the active
position.
1. Check the buttons for obstructions
2. Reset the device
3. If the condition persists, replace the electronics
Simulation Active The device is in simulation mode
and may not be reporting actual
information.
1. Verify that simulation is no longer required
2. Disable Simulation mode in Service Tools
3. Reset the device
Device Status Description Recommended Action