Commissioning
Figure 4-3. Smart Wireless Gateway Explorer page.
AMS Suite Wireless Configurator
When the device has joined the network, it will appear in the Device Manager as illustrated in
Figure 4-4. For HART Wireless transmitter communication, a Rosemount 2051 Wireless DD is
required. To obtain the latest DD, visit the Emerson Process Management Easy Upgrade site at:
http://www2.emersonprocess.com/en-US/documentation/deviceinstallkits.
Figure 4-4. Device Manager
Troubleshooting
If the device is not joined to the network after power up, verify the correct configuration of the
Network ID and Join Key, and that Active Advertising has been enabled on the Gateway. The
Network ID and Join Key in the device must match the Network ID and Join Key of the Gateway.
The Network ID and Join Key may be obtained from the Gateway on the Setup>Network>Set-
tings page of the web server (see Figure 4-5 on page 60). The Network ID and Join Key may be
changed in the wireless device by following the Fast Key sequence shown below.