Section 2: Configuration
May 2013
Configuration
Table 2-1. Variable Mapping
Note
The variable assigned to the primary variable drives the output. This value can be selected as
Pressure or Scaled Variable.
Re-mapping using a Field Communicator
Re-mapping using AMS Device Manager
Right click on the device and select Configure.
1. Select Manual Setup and click on the HART tab.
2. Assign Primary, secondary, tertiary and quaternary variables under Variable Mapping.
3. Click Send.
4. Carefully read the warning and click Yes if it is safe to apply the changes.
2.5.2 Set range points
The Range Values command sets the lower and upper range values used for the percent of range
measurement.
Note
Transmitters are shipped from Rosemount Inc. fully calibrated per request or by the factory
default of full scale (span = upper range limit).
1. From the Home screen, select 2: Configure
2. Select 1: Guided Setup
3. Select 1: Basic Setup
4. Select 5: Range Values
Classic Mapping Scaled Variable Mapping
PV Pressure Scaled Variable
SV Sensor Temperature Pressure
TV Electronics Temperature Sensor Temperature
QV Supply Voltage Supply Voltage
From the HOME screen, enter the fast key sequence
Fast Keys
2, 2, 6, 1
From the HOME screen, enter the fast key sequence
Fast Keys
2, 1, 1, 5