Figure 3-16. Bolt tightening pattern
3. If the PTFE sensor module O-rings have been replaced, the flange bolts should be
re-tightened after installation to compensate for cold flow of the O-rings.
4. If applicable, install flange adapters on the process end of the manifold using the
1.75-in. flange bolts supplied with the transmitter.
Note
Always perform a zero trim on the transmitter/manifold assembly after installation to eliminate
mounting effects. See Section 5: Operation and maintenance, “Sensor Trim” on page 68.
3.5.2 Rosemount 306 Integral Manifold installation procedure
The 306 Manifold is for use only with a 2051T Wireless In-line transmitter.
Assemble the 306 Manifold to the 2051T Wireless In-line transmitter with a thread sealant.
1. Place transmitter into holding fixture.
2. Apply appropriate thread paste or tape to threaded instrument end of the manifold.
3. Count total threads on the manifold before starting assembly.
4. Start turning the manifold by hand into the process connection on the transmitter.