Reference Manual
00809-0100-4102, Rev AA
Section 2: Configuration
May 2013
Configuration
2.3.1 Connection diagrams
Bench hook-up
Connect the bench equipment as shown in Figure 2-1 on page 11, and turn on the Field
Communicator by pressing the ON/OFF key or log into AMS. The Field Communicator or AMS
will search for a HART-compatible device and indicate when the connection is made. If the Field
Communicator or AMS fail to connect, it indicates that no device was found. If this occurs, refer
to Section 6: Troubleshooting.
Field hook-up
Figure 2-1 on page 11 illustrates the wiring for a field hook-up with a Field Communicator or
AMS. The Field Communicator or AMS may be connected at “COMM” on the transmitter Power
Module.
Figure 2-1. Field Communicator Connection
For HART communication, a 2051 WirelessHART DD is required.
2.4 Basic setup
2.4.1 Set device tag
The tag is used to identify the device. You can use an 8 to 32 character tag.
1. From the Home screen, select 2: Configure
2. Select 2: Manual Setup
3. Select 9: Device Information
4. Select 1: Identification
5. Select 1: Tag
Fast Keys
2, 2, 9, 1, 1