Appendix A: Reference Data
May 2013
Specifications and Reference Data
Process Temperature Limits
At atmospheric pressures and above.
A.3.5 Humidity Limits
0–100% relative humidity
A.3.6 Volumetric Displacement
Less than 0.005 in
3
(0,08 cm
3
)
A.3.7 Damping
The Damping command introduces a delay in processing which increases the response time of
the transmitter; smoothing variations in output readings caused by rapid input changes. In the
2051 Wireless pressure transmitter, damping only takes effect when the device is placed in high
power refresh mode and during calibration. In normal power mode, the effective damping is 0.
Note that when the device is in high power refresh mode, battery power will be depleted rapidly.
2051C Coplanar
Silicone Fill Sensor
(1)
(1) Process temperatures above 185 °F (85 °C) require derating the ambient limits by a 1.5:1 ratio.
with Coplanar Flange –40 to 250 °F (–40 to 121 °C)
(2)
(2) 220 °F (104 °C) limit in vacuum service; 130 °F (54 °C) for pressures below 0.5 psia.
with Traditional Flange –40 to 300 °F (–40 to 149 °C)
(2)(3)
(3) -20 °F (-29 °C) is the lower process temperature limit with option code P0.
with Level Flange –40 to 300 °F (–40 to 149 °C)
(2)
with 305 Integral
Manifold
–40 to 300 °F (–40 to 149 °C)
(2)(3)
Inert Fill Sensor
(1)
-40 to 185 °F (–40 to 85 °C)
(4)(5)
(4) 160 °F (71 °C) limit in vacuum service.
(5) Not available for 2051_CA.
2051T In-Line (Process Fill Fluid)
Silicone Fill Sensor
(1)
–40 to 250 °F (–40 to 121 °C)
(2)
Inert Fill Sensor
(1)
–22 to 250 °F (–30 to 121 °C)
(2)
2051L Low-Side Temperature Limits
Silicone Fill Sensor
(1)
–40 to 250 °F (–40 to 121 °C)
(2)
Inert Fill Sensor
(1)
–40 to 185 °F (–40 to 85 °C)
(2)
2051L High-Side Temperature Limits
(Process Fill Fluid)
Syltherm
®
XLT –102 to 293 °F (–75 to 145 °C)
D. C.
®
Silicone 704
(6)
(6) Upper limit of 600 °F (315 °C) is available with 1199 seal assemblies mounted away from the transmitter
with the use of capillaries and up to 500 °F (260 °C) with direct mount extension.
32 to 401 °F (0 to 205 °C)
D. C. Silicone 200 –49 to 401 °F (–45 to 205 °C)
Inert (Halocarbon) –49 to 320 °F (–45 to 160 °C)
Glycerin and Water 5 to 203 °F (–15 to 95 °C)
Neobee M-20
®
5 to 401 °F (–15 to 205 °C)
Propylene Glycol and
Water
5 to 203 °F (–15 to 95 °C)