Emerson Process Management IM-106-340 Oxygen Equipment User Manual


 
Instruction Manual
IM-106-340, Rev. 4.0
May 2006
2-13
Oxymitter 4000
ELECTRICAL
INSTALLATION (WITH
REMOTE
ELECTRONICS)
For Oxymitter 4000 with Remote Electronics
All wiring must conform to local and national codes.
NOTE
To maintain proper earth grounding, ensure a positive connection exists
between the sensor housing, the electronics housing, and earth. The
connecting ground wire must be 14 AWG minimum. Refer to Figure 2-10.
NOTE
Line voltage, signal, and relay wiring must be rated for at least 221°F (105°C).
1. Remove cover (27) from remote electronics.
2. Connect Line Voltage.
a. Connect the line, or L1 wire to the L1 terminal and the neutral, or
L2 wire, to the N terminal (Figure 2-10). The Oxymitter 4000
automatically will configure itself for 90-250 VAC line voltage and
50/60 Hz. The power supply requires no setup.
3. Connect 4-20 mA Signal and Calibration Handshake/Logic I/O Leads
(Figure 2-10). Use individual shielded twisted wire pairs. Terminate the
shield only at the electronics housing.
a. 4-20 mA Signal. The 4-20 mA signal represents the O
2
value and
can also operate the Model 751 Remote Powered Loop LCD Display
or any other loop powered display. Superimposed on the 4-20 mA
signal is HART information that is accessible through a Model
275/375 Handheld Communicator or AMS software.
Disconnect and lock out power before connecting the power supply.
Install all protective covers and safety ground leads after installation. Failure to install covers
and ground leads could result in serious injury or death.
To meet the Safety Requirements of IEC 1010 (EC requirement), and ensure safe operation
of this equipment, connection to the main electrical power supply must be made through a
circuit breaker (min 10 A) which will disconnect all current-carrying conductors during a fault
situation. This circuit breaker should also include a mechanically operated isolating switch.
If not, then another external means of disconnecting the supply from the equipment should
be located close by. Circuit breakers or switches must comply with a recognized standard
such as IEC 947.