North American Certifications
Factory Mutual (FM)
NOTE
For intrinsically safe (IS) outputs on the 8732E output option code B must be selected.
IS outputs for Class I, Division 1, Groups A, B, C, D.
Temp Code – T4 at 60°C
NOTE
For the 8732E transmitters with a local operator interface (LOI) or display, the lower ambient
temperature limit is -20 °C.
N0 Division 2 Approval (All transmitters)
Reference Rosemount Control Drawing 08732-1052 (8732E).
Class I, Division 2, Groups A, B, C, D
Temp Codes – T4 (8712 at 40°C)
T4 (8732 at 60°C: -50 °C Ta 60 °C)
Dust-ignition proof Class II/III, Division 1, Groups E, F, G
Temp Codes – T4 (8712 at 40°C), T5 (8732 at 60°C)
Enclosure Type 4X
N5 Division 2 Approval (All Transmitters)
For sensors with IS electrodes only
Reference Rosemount Control Drawing 08732-1052 (8732E).
Class I, Division 2, Groups A, B, C, D
Temp Codes – T4 (8712 at 40°C),
T4 (8732 at 60°C: -50 °C Ta 60 °C)
Dust-ignition proof Class II/III, Division 1, Groups E, F, G
Temp Codes – T4 (8712 at 40°C), T5 (8732 at 60°C)
Enclosure Type 4X
E5 Explosion-Proof Approval (8732E)
Reference Rosemount Control Drawing 08732-1052
Explosion-Proof for Class I, Division 1, Groups C, D
Temp Code – T6 at 60°C
Dust-ignition proof Class II/III, Division 1, Groups E, F, G
Temp Code – T5 at 60°C
Class I, Division 2, Groups A, B, C, D
Temp Codes – T4 (8732 at 60°C)
Enclosure Type 4X
Canadian Standards Association (CSA)
N0 Division 2 Approval
Reference Rosemount Control Drawing 08732-1051 (8732E)
Class I, Division 2, Groups A, B, C, D
Temp Codes – T4 (8732 at 60°C: -50 °C Ta 60 °C)
Dust-ignition proof Class II/III, Division 1, Groups E, F, G
Temp Codes – T4 (8712 at 40°C), T5 (8732 at 60°C)
Enclosure Type 4X