In Auto mode, OUT reflects the value and status quality of the
output channels.
TROUBLESHOOTING Refer to Table G-6 to troubleshoot transducer block problems.
Table G-6. Troubleshooting
Symptom Possible Causes Corrective Action
Mode will not leave out of
service (OOS).
Target mode not set Set target mode to something other
than OOS.
Resource block The actual mode of the resource block
is OOS. See Appendix F: Resource
Block: and Section 3: Configuration.
PVor SV is BAD Measurement See Diagnostics, Table G-4.
Flow is above
SENSOR_RANGE.EU100.
PV or SV is UNCERTAIN Measurement Flow is above
PRIMARY_VALUE_RANGE.EU100.