Appendix F Resource Block
Parameters and Descriptions . . . . . . . . . . . . . . . . . . . . . . page F-1
Resource Block Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . page F-5
Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page F-5
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page F-6
This section contains information on the resource block for the
Rosemount 8732 Magnetic Flowmeter Transmitter. Descriptions of all
resource block parameters, errors, and diagnostics are included. Also, the
modes, alarm detection, status handling, virtual communication relationships
(VCRs), and troubleshooting are discussed.
Definition The resource block defines the physical resources of the device, such as
measurement and memory. The resource block also handles functionality,
such as shed times, that is common across multiple blocks. The block has no
linkable inputs or outputs, and it performs memory-level diagnostics.
PARAMETERS AND
DESCRIPTIONS
Table F-1 lists all of the configurable parameters of the resource block,
including the descriptions and index numbers for each parameter. Newer
software revisions have added functionality and some index numbers have
changed. To determine the software revision of a transmitter, check the
parameter SOFTWARE_REVISION_MAJOR. The most recent transmitters
have a label on the electronic board stack.
Table F-1. Resource Block
Parameters
Index Number
Parameter Rev 5 Description
ACK_OPTION 38 ACK_OPTION is a selection of whether alarms associated with the function block
will be automatically acknowledged.
ADVISE_ACTIVE 82 Active advisory alarms.
ADVISE_ALM 83 Alarm indicating advisory alarms. These conditions do not have a direct impact on
the process or device integrity.
ADVISE_ENABLE 80 Enables or disables the advisory conditions within a device.
ADVISE_MASK 81 Mask of advisory Alarm. Corresponds bit for bit to the Advisory Active. A bit on
means that the failure is masked out from alarming.
ADVISE_PRI 79 Designates the alarming priority of the advisory alarm.
ALARM_SUM 37 This parameter shows the current alert status, unacknowledged states, unreported
states, and disabled states of the alarms associated with the function block. In the
Rosemount 8732 Magnetic Flowmeter Transmitter, the two resource block alarms
are write alarm and block alarm.
ALERT_KEY 04 ALERT_KEY shows the identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.