Emerson Process Management 8732 Oxygen Equipment User Manual


 
Reference Manual
00809-0100-4663, Rev BA
January 2010
Rosemount 8732
www.rosemount.com
Section 4 Operation
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1
Advanced Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-12
Detailed Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-12
Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-17
INTRODUCTION This section contains information for advanced configuration parameters and
diagnostics.
The software configuration settings for the Rosemount 8732 can be accessed
through a 375 Field Communicator or through a control system. The software
functions for the 375 Field Communicator are described in detail in this
section of the manual. It provides an overview and summary of communicator
functions. For more complete instructions, see the communicator manual.
Before operating the Rosemount 8732 in an actual installation, you should
review all of the factory set configuration data to ensure that they reflect the
current application.
DIAGNOSTICS Diagnostics are used to verify that the transmitter is functioning properly, to
assist in troubleshooting, to identify potential causes of error messages, and
to verify the health of the transmitter and sensor. Diagnostic tests can be
initiated through the use of a 375 Field Communicator or through the control
system.
Rosemount offers several different diagnostic suites providing various
functionality.
Standard diagnostics included with every Rosemount 8732 transmitter are
Empty Pipe detection, Electronics Temperature monitoring, Coil Fault
detection, and various loop and transmitter tests.
Advanced diagnostics suite option one (D01 option) contains advanced
diagnostics for High Process Noise detection and Grounding and Wiring fault
detection.
Advanced diagnostics suite option two (D02 option) contains advanced
diagnostics for the 8714i Meter Verification. This diagnostic is used to verify
the accuracy and performance of the magnetic flow meter installation.
Diagnostic Controls The diagnostic controls menu provides a centralized location for enabling or
disabling each of the diagnostics that are available. Note that for some
diagnostics to be available, a diagnostics suite package is required.
375 Transducer Block
375 Transducer Block, Diagnostics