Emerson Process Management 8732 Oxygen Equipment User Manual


 
Reference Manual
00809-0100-4663, Rev BA
January 2010
Rosemount 8732
F-2
BLOCK_ALM 36 The block alarm is used for all configuration, hardware, connection failure, or
system problems in the block. The cause of the alert is entered in the subcode
field. The first alert to become active will set the active status in the status
parameter. As soon as the unreported status is cleared by the alert reporting task,
another block alert may be reported without clearing the active status, if the
subcode has changed.
BLOCK_ERR 06 This parameter reflects the error status of the hardware or software components
associated with a block. It is a bit string, so multiple errors may be shown.
CLR_FSAFE 30 Writing a Clear to this parameter will clear the device FAULT_ STATE if the field
condition has cleared.
CONFIRM_TIME 33 This parameter represents the minimum time between retries of alert reports.
CYCLE_SEL 20 This parameter is used to select the block execution method for this resource. The
Rosemount 8732 supports the following executions:
Scheduled: Blocks are only executed based on the schedule in FB_START_LIST.
Block Execution: A block may be executed by linking to another block’s completion.
CYCLE_TYPE 19 This parameter identifies the block execution methods available for this resource.
DD_RESOURCE 09 This string identifies the tag of the resource that contains the device description for
this resource.
DD_REV 13 DD_REV is a revision of the DD associated with the resource—used by an
interface device to locate the DD file for the resource.
DEFINE_WRITE_LOCK 60 This parameter is an enumerated value describing the implementation of the
WRITE_LOCK.
DETAILED_STATUS 55 DETAILED_STATUS is an additional status bit string.
DEV_REV 12 This parameter represents the manufacturer revision number associated with the
resource—used by an interface device to locate the DD file for the resource.
DEV_STRING 43 Used to load new licensing into the device. The value can be written but will always
read back with a value of 0.
DEV_TYPE 11 This parameter represents the manufacturer’s model number associated with the
resource—used by interface devices to locate the DD file for the resource
(Rosemount 8732).
DIAG_OPTION 46 Indicates which diagnostics licensing options are enabled.
DISTRIBUTOR 42 References the company that is responsible for the distribution of this device.
DOWNLOAD_MODE 67 DOWNLOAD_MODE gives access to the boot block code for over-the-wire
downloads.
FAILED_ACTIVE 72 Active fail alarms.
FAILED_ALM 73 Alarm indicating a failure within a device which makes the device non-operational.
FAILED_ENABLE 70 Enables or disables the failure conditions within a device.
FAILED_MASK 71 Mask of Failure Alarm. Corresponds bit of bit to the Fail Active. A bit on means that
the failure is masked out from alarming.
FAILED_PRI 69 Designates the alarming priority of the fail alarm.
FAULT_STATE 28 Condition set by loss of communication to an output block, fault promoted to an
output block or physical contact. When FAULT_ STATE condition is set, then output
function blocks will perform their FAULT_ STATE actions.
FB_OPTION 45 Indicates which function block licensing options are enabled.
FEATURES 17 This parameter is used to show supported resource block options.
FEATURE_SEL 18 Used to show selected resource block options. The Rosemount 8732 Magnetic
Flowmeter Transmitter supports the following options:
Unicode: Tells the host to use unicode for string values
Reports: Enables alarms; must be set for alarming to work
Software Lock: Software write locking enabled but not active; WRITE_LOCK must
be set to activate
Hardware Lock: Hardware write locking enabled but not active; WRITE_LOCK
follows the status of the security switch
FINAL_ASSY_NUM 54 FINAL_ASSEMBLY_NUMBER is used for identification purposes and is associated
with the overall field device.
Index Number
Parameter Rev 5 Description