Model9060ZManual
29
SETUP/RUNkey
Pressing this key will put the transmitterinto one of the menu‐driven SETUP, COMMISSIONING or
CALIBRATIONmodes(seechapters6,7and8fordetails).Thefunctionofallthekeyswillthenchange
tothefunctionsthattheyhaveintheSETUPmode.
DISPLAYUP/DOWNkeys
Thedisplaykeysareusedtoscrollthelowerlineupanddownthroughthevarietyofmeasurements
thatareavailableonthelowerline.Foracompletelistofoptionsseechapter6.3.2,LowerLineItems.
ALARMUPkey
IfthereiseitheranewalarmoranactivealarmtheALARMUPkeycanbepressedtoexaminethe
alarmstatus.Thealarmlightwillbeflashingifthereisanewalarmorsteadyifthereisanexisting
alarm.Formoredetailsonthealarmmodeandkeysseechapter9,Alarms.TheSETUPlightwillflash
slowlytoshowthatthetransmitterisnowinthealarmdisplaymode.
ALARMDOWNkey
Whenthetransmitterisdisplayingactivealarms(theALARMUPkeyhasbeenpressed),theALARM
DOWNkeyandtheALARMUPkeyallowtheoperatortoexaminethedate/timeofthealarmandthe
date/timethatthealarmwasacknowledged.
IfthetransmitterwasinRUNmodewhenthiskeyispresseditwillgointothealarmlogdisplaymode.
Seechapter9formoredetails.
ALARMACCEPTkey
TheALARMACCEPTkeyisusedtoacceptanewalarm(seechapter9,Alarms).
GAS1/PURGE1andGAS2/PURGE2keys
Thesetwokeysareusedtoturnonthegas/purgesolenoids.Whenthetransmitterisinthemanual
cal/purgemode(Commissioningfunctions#21and30)thesolenoidwillbeactivatedforaslongas
thekeyispressed.Whenthetransmitterisintheautocal/purgemodetheautomaticcal/purge
cycleisstarted.Thecyclecanbestoppedbypressingthesamekeyagain.
5.3.2KeypadinSETUP/COMMISSIONING/CALIBRATIONmodes
NOTE: In order to enter either COMMISSIONING or CALIBRATION modes, the corresponding DIP
switchonthe1732‐1PCBmustbeturnedon.
FromRUNmode,iftheSETUP/RUNkeyispressedonce,thetransmitterwillgointotheSETUPmode.
FromRUNmode,iftheSETUP/RUNkeyispressedandheldfor2seconds,thetransmitterwillgointo
theCOMMISSIONINGmode.
FromRUNmode,iftheSETUP/RUNkeyispressedandheldfor4seconds,thetransmitterwillgoint
o
theCALIBRATIONmode.
Thefollowingkeyfunctionsarethenavailableinalloftheabovemodes.
SETUP/RUNkey
PressingtheSETUP/RUNkeywhileinanyofthesetupmodeswillreturnthetransmittertotheRUN
mode.