4. To enable Multi-Step Ramp, click on the white dot (Òradio buttonÓ) next to it. A black
dot in the circle indicates that the function has been selected. The gray values in the
Multi-Step Ramp panel, and in the the Holdback Band, Termination State, and
Repeats entry boxes will become black, indicating that they can be edited. The
Power Fail Resume and Continuous Repeat labels will also become black, indicating
that these options are available for selection. The values in the Multi-Step Ramp
panel represent the values stored in the controllerÕs recipe parameters. (The units of
measure match those selected for the display units parameter.)
5. Use the Termination State dropdown list to specify what you want to happen to the
controller when execution of the recipe has been completed.
6. Use the Repeats box to enter the number of times you want the recipe to execute
each time it is run. If you want the recipe to run once, leave the Repeats value at the
default, zero. If you want the recipe to cycle continuously once started, click on the
box to the left of ÒContinuousÓ. The box will be checked, indicating that the option
has been selected.
7. Enter a Holdback value of at least 1, or disable holdback.
16
16
If you are concerned that your process might not be responsive enough to reach the soak levels in the
specified ramp times, use the holdback feature. If holdback is enabled, then the system will not allow the
setpoint to become more than n engineering units away from the process value, where n is the Holdback
value. The system will Òhold backÓ the SP until the PV has had a chance to catch up. This has the effect
of Òstopping the clockÓ on the SP ramp time until the PV is within n units of the SP.
The specified holdback value n will also be applied to the soak level. If the temperature falls more than n
units from the soak level, then the clock is stopped on the soak time until the PV is again within n units of
the SP specified for the soak level.