Looking for a device Polling for multidropped devices at addresses 1–15.
Local buttons
operator error ON
Illegal pressure applied during zero or span operation. Repeat
the process after verifying the correct pressures.
Mark as read only
variable on hotkey
menu?
Asks whether the user should be allowed to edit the variable
from the hotkey menu if the item being added to the hotkey
menu is a variable.
Module EEPROM
write failure ON
Message sent to the module from the HART signal failed.
Return to Rosemount Nuclear Instruments, Inc. for repair.
No device
configuration in
configuration
memory
There is no configuration saved in memory available to
re-configure off-line or transfer to a device.
No Device Found Poll of address zero fails to find a device, or poll of all
addresses fails to find a device if auto-poll is enabled.
No hotkey menu
available for this
device.
There is no menu named “hotkey” defined in the device
description for this device.
No pressure updates
ON
No pressure updates being received from the sensor module.
Verify that the sensor module ribbon cable is attached correctly.
Return to Rosemount Nuclear Instruments, Inc. for repair.
No offline devices
available.
There are no device descriptions available to be used to
configure a device offline.
No simulation
devices available.
There are no device descriptions available to simulate a
device.
No temperature
updates ON
No temperature updates being received from the sensor
module. Verify that the sensor module ribbon cable is attached
correctly. Return to Rosemount Nuclear Instruments, Inc. for
repair.
No
UPLOAD_VARIABLE
S in ddl for this
device
There is no menu named “upload_variables” defined in the
device description for this device. This menu is required for
offline configuration.
No Valid Items The selected menu or edit display contains no valid items.
OFF KEY DISABLED Appears when the user attempts to turn the HC off before
sending modified data or before completing a method.
Online device
disconnected with
unsent data. RETRY
or OK to lose data.
There is unsent data for a previously connected device. Press
RETRY to send data, or press OK to disconnect and lose
unsent data.
Out of memory for
hotkey
configuration. Delete
unnecessary items.
There is no more memory available to store additional hotkey
items. Unnecessary items should be deleted to make space
available.
Overwrite existing
configuration
memory
Requests permission to overwrite existing configuration either
by a device-to-memory transfer or by an offline configuration.
User answers using the softkeys.
Press OK... Press the OK softkey. This message usually appears after an
error message from the application or as a result of HART
communications.
Restore device
value?
The edited value that was sent to a device was not properly
implemented. Restoring the device value returns the variable to
its original value.