Emerson Process Management 3051N Sleep Apnea Machine User Manual


 
Reference Manual
00809-0100-4808, Rev CA
June 2008
2-19
Rosemount 3051N
Recall Factory Trim The Recall Factory Trim commands allow the restoration of the as-shipped
factory settings of the sensor trim and analog output trim.
Recall Factory Trim—
Sensor Trim
Resets the transmitter sensor trim to the as-shipped factory settings. The
Recall Factory Trim—Sensor Trim command can be useful for recovering
from an inadvertent zero trim of an absolute pressure unit.
Recall Factory Trim—
Analog Output
Resets the transmitter analog output trim to the as-shipped
factory settings. The Recall Factory Trim—Analog Output Trim command can
be useful for recovering from an inadvertent zero trim on an absolute pressure
transmitter.
Analog Output Trim The Analog Output Trim commands allow you to adjust the transmitter’s
current output at the 4 and 20 mA points to match the plant standards. This
command adjusts the digital to analog signal conversion (see Figure 2-7).
Digital-to-Analog Trim To perform a digital-to-analog trim with a HART Communicator, perform the
following procedure.
1. From the ONLINE screen, select 1 Device setup, 2 Diag/Service,
3 Calibration, 2 Trim Analog Output, 1 Digital-to-Analog Trim. Select
OK after you set the control loop to manual (see “Setting the Loop to
Manual” on page 2-5).
2. Connect an accurate reference ammeter to the transmitter at the
CONNECT REFERENCE METER prompt. To do so, connect the
positive lead to the positive terminal and the negative lead to the test
terminal in the transmitter terminal compartment, or shunt the
transmitter power through the reference meter at some point.
3. Select OK after connecting the reference meter.
4. Select OK at the SETTING FLD DEV OUTPUT TO 4 MA prompt. The
transmitter outputs 4.00 mA.
5. Record the actual value from the reference meter, and enter it at the
ENTER METER VALUE prompt. The communicator prompts you to
verify whether or not the output value equals the value on the
reference meter.
6. Select 1Yes if the reference meter value equals the transmitter
output value, or 2No if it does not.
IF
you select 1Yes, THEN proceed to Step 7.
IF
you select 2No, THEN repeat Step 5.
7. Select OK at the SETTING FLD DEV OUTPUT TO 20 MA prompt,
and repeat Steps 5 and 6 until the reference meter value equals the
transmitter output value.
8. Select OK after you return the control loop to automatic control.
Digital-to-Analog Trim
Using Other Scale
The Scaled D/A Trim command matches the 4 and 20 mA points to a
user-selectable reference scale other than 4 and 20 mA (1 to 5 volts if
measuring across a 250 ohm load, or 0 to 100 percent if measuring from a
DCS, for example). To perform a scaled D/A trim, connect an accurate
reference meter to the transmitter and trim the output signal to scale as
outlined in the Output Trim procedure.
HART Comm. 1, 2, 3, 4, 1
HART Comm. 1, 2, 3, 4, 2
HART Comm. 1, 2, 3, 2, 1
HART Comm. 1, 2, 3, 2, 2