Fast Key Sequences The Fast Key sequence is a sequence of numerical button presses,
corresponding to the menu options that lead you to a given task. Use Table
A-1, an alphabetical listing of most on-line functions, to find the corresponding
HART fast key sequences. These codes are applicable only to Rosemount
3051N transmitters and the HART Communicator.
Hot Key options The Hot Key menu is a user-definable menu that can store shortcuts for up to
20 of your most frequently performed tasks. For example, if you change
device tags, and damping often, you can add options for these functions to
the Hot Key menu. Once you are Online, the Hot Key will automatically
appear in the toolbar. To add a custom option to the Hot Key menu, refer to
the Rosemount 375 Communicator user manual.
To use a Hot Key option, you must first properly connect the Rosemount 375
Field Communicator to a device. You can access the Hot Key menu from any
online window. To use a Hot Key option:
1. Connect the Rosemount 375 Field Communicator to a HART loop or
device.
2. Tap the Hot Key. The Hot Key menu is displayed.
3. Double-tap the desired option.
DIAGNOSTIC
MESSAGES
The following pages contain a list of messages used by both of the
Rosemount 275 and Rosemount 375 HART Communicators (HC) and their
corresponding descriptions.
Variable parameters within the text of a message are indicated with
<variable parameter>.
Reference to the name of another message is identified by
[another message].
Message Description
1k snsr EEPROM
error-factory ON
Return to Rosemount Nuclear Instruments, Inc. for repair.
1k snsr EEPROM
error-user-no out ON
Use the HART communicator to reset the following parameters:
remote seal isolator, remote seal fill fluid, flange material, o-ring
material, transmitter type, remote seal type, flange type, meter
type, number of remote seals.
1k snsr EEPROM
error-user ON
Perform a full trim to recalibrate the transmitter.
4k micro EEPROM
error-factory ON
Return to Rosemount Nuclear Instruments, Inc. for repair.
4k micro EEPROM
error-user-no out ON
Use the HART communicator to reset the message field.
4k micro EEPROM
error-user ON
Use the HART communicator to reset the following parameters:
units, range values, damping, analog output, transfer function,
tag, scaled meter values. Perform a d/a trim to ensure that the
error is corrected.
4k snsr EEPROM
error-factory ON
Return to Rosemount Nuclear Instruments, Inc. for repair.
4k snsr EEPROM
error-user ON
Use the HART communicator to reset the temperature units
and the calibration type.