Emerson Process Management 3051N Sleep Apnea Machine User Manual


 
Reference Manual
00809-0100-4808, Rev CA
June 2008
3-3
Rosemount 3051N
FIGURE 3-1. Typical
Installation Flowchart.
START HERE
Bench
Calibration?
Field Install
No
Configure
(Section 2)
Set Units
Set Range
Points
Set Output
Type
Set Damping
Verify
Apply Pressure
Yes
Within
Specifica-
tions?
Yes
No
Refer to
Section 4
Troubleshooting
Check Jumpers
and Switches
(page 2-2)
Mount
Transmitter
(pages 3-4–3-14)
Wire Transmitter
(pages 3-12–3-14)
Power
Transmitter
(page 3-12)
Check Process
Connection
for Leaks
(page 3-12)
Confirm
Transmitter
Configuration
(page A-4)
Trim Transmitter
for Mounting
Effects
(page 2-15)
Done