Emerson Process Management 3051N Sleep Apnea Machine User Manual


 
Reference Manual
00809-0100-4808, Rev CA
June 2008
Rosemount 3051N
6-6
Some non-volatile memory faults are user-addressable. Use a HART
Communicator to diagnose the error and determine if it is repairable. Any
error message that ends in “FACTORY” is not repairable. In cases of non
user-addressable errors, you must replace the transmitter. Contact
Rosemount Nuclear Instruments Inc. at (952) 949-5210 if you need
assistance.
FAIL ELECT
The transmitter electronics board is malfunctioning due to an internal fault.
Some of the FAIL ELECT errors are user-addressable. Use a HART
Communicator to diagnose the error and determine if it is repairable. Any
error message that ends in “FACTORY” is not repairable. In cases of non
user-repairable errors, you must replace the transmitter. Contact Rosemount
Nuclear Instruments, Inc. at (952) 949-5210 if you need assistance.
FAIL CONFIG
A memory fault has been detected in a location that could effect transmitter
operation, and is user-addressable. To correct this problem, use a HART
Communicator to interrogate and reconfigure the appropriate portion of the
transmitter memory. Contact Rosemount Nuclear Instruments, Inc. at
(952) 949-5210 if you need assistance.
Warnings Warnings appear on the LCD meter display to alert you of user-repairable
problems with the transmitter, or current transmitter operations. Warnings
appear alternately with other transmitter information until the warning
condition is corrected or the transmitter completes the operation that warrants
the warning message.
PRESS LIMIT
The process variable read by the transmitter is outside of the transmitter’s
range.
TEMP LIMIT
The secondary temperature variable read by the transmitter is outside of the
transmitter’s range.
CURR SATURD
The pressure read by the module is outside of the specified range, and the
analog output has been driven to saturation levels. See “Failure Mode Alarm”
in Section 2.
LOOP TEST
A loop test is in progress. During a loop test or 4–20 mA trim, the analog
output is set to a fixed value. The meter display alternates between the
current selected in milliamps and “LOOP TEST.”
XMTR INFO
A non-volatile memory fault has been detected in the transmitter memory by
the memory verification routine. The memory fault is in a location containing
transmitter information. To correct this problem, use a HART Communicator to
interrogate and reconfigure the appropriate portion of the transmitter memory.
This warning does not effect the transmitter operation. Contact Rosemount
Nuclear Instruments Inc. at (952) 949-5210 if you need assistance.