Emerson OCX 8800 Oxygen Equipment User Manual


 
Instruction Manual
IM-106-880, Rev 1.0
January 2007
OCX 8800
B-6
Figure B-6. SPA Configuration Menu
for OCX 8800 Communication
37390003
TRIM
OUT
Ü SET MSTR ÜôPRIM
Ü SET FUCT ÜôNRML
Ü NUM VARS Üô02
Ü NUM TRYS Üô03
Ü EXIT HART Ü SGNL SRCE
Ü AOUT SRCE ÜôSV
Ü AL2 SRCE ÜôPV
Ü AL3 SRCE ÜôPV
Ü AL4 SRCE ÜôPV
Ü EXIT SRCE Ü FLT SRCE
ê CONF OPTS
Ü SET LINR ÜôLINR OFF
Ü PV SCLE ÜôAUTO
Ü DSPL EGU ÜôCSTM ÜôPPM
(select P, select P, select M)
Ü DSPL SRCE ÜôSV
Ü AL2 SEL Ü AL2 FLT
ê SET FAIL Ü FAIL LOW
ê EXIT OPTS Ü SET EGU
Ü PV EGU ÜôPCT
Ü SV EGU ÜôCSTM ÜôPPM
(select P, select P, select M)
Ü EXIT EGU Ü SCLE INPT
Ü PV SCLE Ü PV ZERO ô 0000 PCT
Ü PV FULL ô 25 PCT
Ü
SCLE SV Ü SET ZERO ô 0000 PPM
Ü SET FULL ô 1000 PPM
Ü EXIT SCLE Ü SCLE DSPL
Ü PV DSPL
Ü SET ZERO Üô0000 PCT
Ü SET FULL Üô25 PCT
Ü SV DSPL
Ü SET ZERO Üô0000 PPM
Ü SET FULL Üô1000 PPM
Ü EXIT DSPL Ü SCLE OUT
Ü SET ZERO Üô4.000 MA
Ü SET FULL Üô20.00 MA
Ü EXIT Z/FS
Ü TRIM OUT
Ü TRIM ZERO Üô4.000 MA
Ü TRIM FULL Üô20.00 MA
Ü EXIT TRIM Ü CONF ALRM
SGNL
SRCE
FLT
SRCE
CONF
OPTS
SET
EGU
SCLE
INPT
SET
HART
SCLE
DSPL
SCLE
OUT
CONF
ALRM
SCLE INPT
SCLE DSPL
Refer to
SPA manual
for settings or
ê PASS WORD
CONF
EXIT
PASS
WORD
ê CONF EXIT
Ü SPA setup complete;
observe process value display.