26 Micro Motion
®
Series 3000 MVD Transmitters
Configuring the NOC Application
7. Set the parameters in the Compensations menu as desired.
•For
Transient Bubble Remediation, see Section 2.3.4 for a discussion of this feature, and
see Section 4.6 for additional setup instructions.
•For
Transient Mist Remediation, see Section 2.3.6 for a discussion of this feature, and
see Section 4.8 for additional setup instructions.
•For
Pressure Compensated Density, see Section 2.3.2 for a discussion of this feature,
and see Section 4.5 for additional setup instructions.
•For
Shrinkage Factors, see Section 2.3.3 for a discussion of this feature. To “disable”
shrinkage factors, set them to 1.0.
8. If desired, configure discrete outputs, milliamp outputs, or the frequency output to report NOC
data. To do this, refer to the manual entitled Series 3000 MVD Transmitters and Controllers:
Configuration and Use Manual and:
a. Assign the desired process variable to the output. Available NOC process variables are
listed in Table 4-2.
b. Configure other output parameters as desired.
Table 4-2 Assigning NOC process variables to outputs
NOC process variable
Can be assigned to
Discrete outputs Milliamp outputs Frequency output
TBR event
(1)
(1) ON = TBR active; OFF = TBR inactive.
✓
External water cut ✓
Uncorrected oil volume rate ✓✓
Uncorrected water cut ✓
Uncorrected water volume rate ✓✓
Back flow rate
✓✓
Net oil flow rate
✓✓
Net water cut
✓
Gross volume rate
✓✓
Net water flow rate
✓✓
Average uncorrected oil rate
✓
Average uncorrected water cut
✓
Average uncorrected gross rate
✓
Average uncorrected water rate
✓
Average back flow rate
✓
Average net oil flow rate
✓
Average net water cut
✓
Average gross volume rate
✓
Average net water rate
✓
Average gas volume flow rate
✓