5-5
Rosemount 2051
RESOURCE BLOCK This section describes error conditions found in the Resource block. Read
Table 5-2 through Table 5-4 to determine the appropriate corrective action.
Table 5-2. Resource Block
BLOCK_ERR messages
Block Errors
Table 5-2 lists conditions reported in the BLOCK_ERR parameter.
Table 5-3. Resource Block
SUMMARY_STATUS messages
Table 5-4. Resource Block
DETAILED_STATUS with
recommended action messages
Condition Name and Description
Other
Simulate Active: This indicates that the simulation switch is in place. This is not an indication
that the I/O blocks are using simulated data.
Device Fault State Set
Device Needs Maintenance Soon
Memory Failure: A memory failure has occurred in FLASH, RAM, or EEPROM memory
Lost Static Data: Static data that is stored in non-volatile memory has been lost.
Lost NV Data: Non-volatile data that is stored in non-volatile memory has been lost.
Device Needs Maintenance Now
Out of Service: The actual mode is out of service.
Condition Name
Uninitilized
No repair needed
Repairable
Call Service Center
Condition Name Recommended Action
LOI Transducer block error 1. Restart processor
2. Check display connection
3. Call service center
Sensor Transducer block error. 1. Restart processor
2. Check sensor module cable
3. Call service center
Mfg. Block integrity error 1. Restart processor
2. Call service center
Non-Volatile memory integrity error 1. Restart processor
2.Call service center
ROM integrity error 1. Restart processor
2. Call service center