Block/Transducer Errors The following conditions are reported in the BLOCK_ERR and XD_ERROR
parameters. Conditions in bold type are available. Conditions in italics are
inactive for the Transducer block and are given here only for your reference.
SENSOR_TYPE 20 Type of sensor connected with the transducer block.
Valid sensor types are the following:
117 = Capacitance
124 = Strain Gauge
ST_REV 01 The revision level of the static data associated with the function block.
STRATEGY 03 The strategy field can be used to identify grouping of blocks.
TAG_DESC 02 The user description of the intended application of the block.
TB_DETAILED_STATUS 31 Indicates the state of the transmitter. The parameter contains specific codes relating to
the transducer block and the pressure sensor specifically.
TRANSDUCER_DIRECTORY 09 Directory that specifies the number and starting indices of the transducers in the
transducer block.
TRANSDUCER_TYPE 10 Identifies the transducer that follows.
100 = Standard pressure with calibration
UPDATE_EVT 07 This alert is generated by any change to the static data.
XD_ERROR 11 Provides additional error codes related to transducer blocks.
Parameter
Index
Number
Description
Condition
Number
Condition Name and Description
0 Other
1 Block Configuration Error
2 Link Configuration Error
3 Simulate Active
4 Local Override
5 Device Fault State Set
6 Device Needs Maintenance Soon
7 Input failure/process variable has bad status
8 Output Failure
9 Memory Failure
10 Lost Static Data
11 Lost NV Data
12 Readback Check Failed
13 Device Needs Maintenance Now
14 Power Up: The device was just powered-up.
15 Out of Service: The actual mode is out of service.
17 General Error: A general error that cannot be specified below occurred
20 Electronics Failure: An electrical component failed.
22 I/O Failure: An I/O failure occurred.
23 Data Integrity Error: Data stored in the device is no longer valid due to a
non-volatile memory checksum failure, a data verify after write failure, etc.
25 Algorithm Error: The algorithm used in the transducer block produced an
error due to overflow, data reasonableness failure, etc.