ELECTRICAL
CONSIDERATIONS
NOTE
Make sure all electrical installation is in accordance with national and local code
requirements.
Conduit Installation
Recommended conduit connections are shown in Figure 2-12.
Figure 2-12. Conduit Installation
Diagrams.
If all connections are not sealed, excess moisture accumulation can damage the
transmitter. Make sure to mount the transmitter with the electrical housing positioned
downward for drainage. To avoid moisture accumulation in the housing, install wiring
with a drip loop, and ensure the bottom of the drip loop is mounted lower than the
conduit connections or the transmitter housing.
Sealing
Compound
Conduit
Lines
CORRECT