Emerson Process Management 2051 Sleep Apnea Machine User Manual


 
Reference Manual
00809-0200-4101, Rev AA
July 2008
C-11
Rosemount 2051
Block Errors
The table below lists conditions reported in the BLOCK_ERR parameter.
Conditions in bold type are available. Conditions in italics are inactive for the
Resource block and are given here only for your reference.
Condition
Number
Condition Name and Description
0Other
1 Block Configuration Error: A feature in FEATURES_SEL is set that is not
supported by FEATURES or an execution cycle in CYCLE_SEL is set that
is not supported by CYCLE_TYPE.
3 Simulate Active: This indicates that the simulation jumper is in place. This
is not an indication that the I/O blocks are using simulated data.
4 Local Override
5 Device Fault State Set
6 Device Needs Maintenance Soon
7 Input failure/process variable has bad status
9 Memory Failure: A memory failure has occurred in FLASH, RAM, or
EEROM memory
10 Lost Static Data: Static data that is stored in non-volatile memory
has been lost.
11 Lost NV Data: Non-volatile data that is stored in non-volatile memory
has been lost.
12 Readback Check Failed
13 Device Needs Maintenance Now
14 Power Up: The device was just powered-up.
15 Out of Service: The actual mode is out of service.