Hazardous Area OCX 8800
Figure 7-27. Input Selector Function Block Schematic
Block Errors Table 7-34 lists the conditions reported in the BLOCK_ERR parameter.
Conditions in italics are inactive for the ISEL block and are listed for reference
only.
Table 7-34. Block Error
Conditions
Modes The ISEL function block supports three modes of operation as defined by the
MODE_BLK parameter:
Manual (Man) The block output (OUT) may be set manually.
Automatic (Auto) OUT reflects the selected value.
Out of Service (O/S) The block is not processed. The BLOCK_ERR
parameter shows Out of Service. In this mode, changes caNn be made
to all configurable parameters. The target mode of a block may be
restricted to one or more of the supported modes.
OUT
IN_1
IN_2
IN_3
39930025
SELECTOR
IN_4
DISABLE_1
DISABLE_2
DISABLE_3
DISABLE_4
OP_SELECT
Selection
Algorithm
SEL_TYPE
MIN_GOOD
Condition
Number
Condition Name and Description
0 Other: The output has a quality of uncertain.
1 Block Configuration Error
2 Link Configuration Error
3 Simulate Active
4 Local Override: The actual mode is LO.
5 Device Fault State Set
6 Device Needs Maintenance Soon
7 Input Failure/Process Variable has Bad Status: One of the inputs is Bad or not
connected.
8 Output Failure: The output has the quality of Bad.
9 Memory Failure: A memory failure has occurred in FLASH, RAM, or EEROM
memory.
10 Lost Static Data
11 Lost NV Data
12 Readback Check Failed
13 Device Needs Maintenance Now
14 Power Up: The device w as just pow ered-up.
15 Out of Service: The actual mode is out of service.