Emerson Process Management OCX 8800 Oxygen Equipment User Manual


 
Instruction Manual
IM-106-880C, OI
September 2009
Hazardous Area OCX 8800
7-42
Table 7-27. BLOCK _ERR
Conditions
Modes The PID function block supports the following modes:
Manual (Man)—The block output (OUT) may be set manually.
Automatic (Auto)—The SP may be set manually and the block algorithm
calculates OUT.
Cascade (Cas)—The SP is calculated in another block and is provided to the
PID block through the CAS_IN connection.
RemoteCascade (RCas)—The SP is provided by a host computer that writes
to the RCAS_IN parameter.
RemoteOutput (Rout)—The OUT is provided by a host computer that writes
to the ROUT_IN parameter.
Local Override (LO)—The track function is active. OUT is set by TRK_VAL.
The BLOCK_ERR parameter shows Local override.
Initialization Manual (IMan)—The output path is not complete (for example,
the cascade-to-slave path might not be open). In IMan mode, OUT tracks
BKCAL_IN.
Out of Service (O/S)—The block is not processed. The OUT status is set to
Bad: Out of Service. The BLOCK_ERR parameter shows Out of service.
You can configure the Man, Auto, Cas, and O/S modes as permitted modes
for operator entry.
Condition
Number
Condition Name and Description
0Other
1 Block Configuration Error: The BY_PASS parameter is not configured and
is set to 0, the SP_HI_LIM is less than the SP_LO_LIM, or the
OUT_HI_LIM is less than the OUT_LO_LIM.
2 Link Configuration Error
3 Simulate Active
4 Local Override: The actual mode is LO.
5 Device Fault State Set
6 Device Needs Maintenance Soon
7 Input Failure/Process Variable has Bad Status: The parameter linked to IN
is indicating a Bad status.
8 Output Failure
9 Memory Failure
10 Lost Static Data
11 Lost NV Data
12 Readback Check Failed
13 Device Needs Maintenance Now
14 Power Up
15 Out of Service: The actual mode is out of service.