Emerson 705 Pacemaker User Manual


 
51
Reference Manual
00809-0200-4705, Rev AA
Appendix B: Product Certifications
May 2015
Product Certifications
N6 Canada Division 2, Nonincendive
Certificate: CSA 70011131
Standards: CAN/CSA C22.2 No. 0-10, CAN/CSA C22.2 No. 94-M91,
CSA Std C22.2 No. 213-M1987 (R2013), CAN/CSA-60079-0 - 2011,
CAN/CSA Std C22.2 No. 60529 - 2005, CAN/CSA-C22.2 No. 61010-1 - 2012
Markings: Suitable for Class 1, Division 2, Groups A, B, C, D T4;
T4 (-50 °C T
a
+70 °C);
Type 4X; IP66;
Special Conditions for Safe Use (X):
1. For use only with the Model 701P or Rosemount P/N 753-9220-XXXX Smart Power
Battery Module.
2. The surface resistivity of the antenna is greater than 1GΩ. To avoid electrostatic
charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.
Europe
I1 ATEX Intrinsic Safety
Certificate: Baseefa14ATEX0375X
Standards: EN 60079-0: 2012, EN 60079-11: 2012
Markings: II 1 G Ex ia IIC T4 Ga, T4(-60 °C T
a
+70 °C)
For use with Rosemount SmartPower
power module part number 753-9220-0001, or
for use with Emerson SmartPower option 701PBKKF.
Special Conditions for Safe Use (X):
1. The surface resistivity of the antenna is greater than 1GΩ. To avoid electrostatic
charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.
2. The 705 enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however, care should be taken to protect it from impact or
abrasion if located in a Zone 0 area.
Totalizer terminal parameters Turbine meter parameters
V
OC
/U
O
= 2.5 V V
MAX
/U
i
= 10 V
I
SC
/I
O
= 253 μA I
MAX
/I
i
= 1 mA
P
MAX
/P
O
= 640 μW P
MAX
/P
i
= 1 mW
Ca/C
O
= 2.9 μF N/A
C
i
= 2.2 nF N/A
La/L
O
= 500 mH N/A
L
i
= 4.7 mH N/A
Totalizer terminal parameters Turbine meter parameters
U
O
= 2.5 V U
i
= 10 V
I
O
= 5.6 mA I
i
= 10 mA
P
O
= 13.9 mW P
i
= 1 mW
C
i
= 2.2 nF N/A
L
i
= 4.7 mH N/A