Section 4: Commissioning
May 2015
Commissioning
4.2 Configuring the transmitter to communicate with
the wireless network
In order to communicate with the Smart Wireless Gateway, and ultimately the Host System, the
transmitter must be configured to communicate with the wireless network. This step is the
wireless equivalent of connecting wires from a transmitter to the Host System. Using a Field
Communicator or AMS
®
Wireless Configurator, enter the Network ID and Join Key so that they
match the Network ID and Join Key of the gateway and other devices in the network. If the
Network ID and Join Key are not identical, the 705 Transmitter will not communicate with the
network. The Network ID and Join Key may be obtained from the Smart Wireless Gateway on
the Setup>Network>Settings page on the web server, shown in Figure 4-1.
Figure 4-1. Gateway Network Settings