Emerson 705 Pacemaker User Manual


 
50
Reference Manual
00809-0200-4705, Rev AA
Appendix B: Product Certifications
May 2015
Product Certifications
USA
I5 U.S.A. Intrinsically Safe (IS)
Certificate: CSA 70011131
Standards: FM 3600 – 2011, FM 3610 – 2010, UL Standard 50 – Eleventh Edition,
UL 61010-1 – 3
rd
Edition, ANSI/ISA-60079-0 (12.00.01) – 2013,
ANSI/ISA-60079-11 (12.02.01) – 2013, ANSI/IEC 60529 – 2004
Markings: IS CL I, DIV 1, GP A, B, C, D T4; Class 1, Zone 0, AEx ia IIC T4 Ga;
T4 (-50 °C T
a
+70 °C) when installed per Rosemount drawing 00705-1020;
Type 4X; IP66;
N5 U.S.A. Division 2, Nonincendive
Certificate: CSA 70011131
Standards: FM 3600 – 2011, FM 3611 – 2004, UL Standard 50 – Eleventh Edition,
UL 61010-1 (3
rd
Edition), ANSI/IEC 60529 – 2004
Markings: NI CL I, DIV 2, GP A, B, C, D T4;
T4 (-50 °C T
a
+70 °C);
Type 4X; IP66;
Special Conditions for Safe Use (X):
1. For use only with the Model 701P or Rosemount P/N 753-9220-XXXX Smart Power
Battery Module.
2. The surface resistivity of the antenna is greater than 1GΩ. To avoid electrostatic
charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.
Canada
I6 Canada Intrinsically Safe (IS)
Certificate: CSA 70011131
Standards: CAN/CSA C22.2 No. 0-10, CAN/CSA C22.2 No. 94-M91,
CSA Std C22.2 No.142-M1987, CAN/CSA-60079-0 - 2011,
CAN/CSA-60079-11 - 2014, CSA Std C22.2 No. 60529 - 2005,
CAN/CSA-C22.2 No. 61010-1 - 2012
Markings: IS CL I, DIV 1, GP A, B, C, D T4;
Ex ia IIC T4 Ga,
T4; T4 (-50 °C T
a
+70 °C)
when installed per Rosemount drawing 00705-1020;
Type 4X; IP66;
Totalizer terminal parameters Turbine meter parameters
V
OC
/U
O
= 2.5 V V
MAX
/U
i
= 10 V
I
SC
/I
O
= 253 μA I
MAX
/I
i
= 1 mA
P
MAX
/P
O
= 640 μW P
MAX
/P
i
= 1 mW
C
i
= 2.2 nF N/A
C
a
/C
O
= 2.9 μF N/A
L
i
= 4.7 mH N/A
L
a
/L
O
= 500 mH N/A