Section 5: Operation and Maintenance
May 2015
Operation and Maintenance
To reset the total of the 705 via Modbus, follow the steps below.
1. Navigate to Modbus connection.
2. Map 705.Accumulaor_Reset.
3. Submit.
To reset the total of the 705 via OPC, follow the steps below.
1. Navigate to OPC connection.
2. Map 705.Accumulaor_Reset.
3. Submit.
To reset the total of the 705 via EtherNet/IP, follow the steps below.
1. Navigate to EtherNet/IP connection.
2. Map 705.Accumulaor_Reset.
3. Submit.
5.6 Reset/Restore device
The 705 Totalizer can be reset remotely over the wireless network, or locally via the wired
maintenance port. Resetting the device will cause the device to temporarily drop offline and
rejoin to the configured wireless network. When resetting the device, you can choose to reset
the device with the same configuration as it already has, or to revert the configuration settings
to the original values that were present when the device left the manufacturer. When reverting
the configuration settings to original values, not that the turbine meter K-factor will also be
reverted, so the turbine meter should be verified to ensure the correct K-factor is being used.
5.7 How to suspend (pause) the totalization in the
device - even though there is still active flow in
the process
The 705 allows the totalization to be stopped, which will hold the current totalized volume value
and ignore any new input pulses. This can be done through a host connection to the wireless
gateway.
Fast keys
3, 5, 2