Emerson 705 Pacemaker User Manual


 
8
Reference Manual
00809-0200-4705, Rev AA
Section 2: Configuration
May 2015
Configuration
Wiring the transmitter
For the R1 option (remote mount), if the turbine meter or pulse output device is installed in a
high-voltage environment and a fault condition or installation error occurs, the sensor leads and
transmitter terminals could carry lethal voltage. Use extreme caution when making contact
with the leads and terminals.
Use the following steps to wire the sensor and power supply to the transmitter:
1. Remove the transmitter enclosure cover.
2. Attach the turbine meter leads according to the diagram Figure 2-1 on page 8.
Note
For noisy electrical environments, it is best practice to ground the loop accordingly.
3. Connect the Black Power Module.
4. Verify the connection and power by viewing the LCD display and seeing the power up
sequence.
5. Replace the cover and tighten.
Figure 2-1. 705 Terminal Block
A. Pulse input connection
B. HART
®
terminal connection
C. Terminal block ground connection
Note
Connections are not polarity sensitive.
2.2 Configuring the transmitter on the bench
When using a Field Communicator, any configuration changes must be sent to the transmitter
using the Send key (F2). AMS Wireless Configurator configuration changes are implemented
when the Apply button is clicked.
A
C
B