Daniel 3410 Series Ultrasonic Gas Flow Meter Installation Manual Section 2: Mechanical installation
3-9000-759 Rev D June 2014
Piping recommendations 31
Figure 2-6 Piping recommendations Uni-directional with flow conditioner
Figure 2-7 Piping recommendations Bi-directional flow with flow conditioner
All pipe lengths are minimum:
D = Nominal pipe size in inches (i.e. 6” pipe size; 10 D = 60 in)
P = Pressure measurement location
T = Temperature measurement location
http://www2.emersonprocess.com/en-US/brands/daniel/Flow/ultrasonics/Pages/Ultrasonic-
Series-3400.aspx
The meter is provided with dowel pins to align the meter body bore with the bore of the
mating piping.
Flow conditioner: Daniel Profiler or CPA 50E
Straightening device
Straightening device
Flow conditioner: Daniel Profiler or CPA 50E
To access the product datasheet from the Daniel products page (above link), select the Daniel
Gas Ultrasonic Flow Meter link, click the Documentation tab, expand the Data Sheets -
Bulletins - Catalogs tab, then select the Data Sheet.