RE-DM4 and RE-DM6 RADIA Eclipse Dimmer Modules
High-Voltage Connections
FIG. 15 shows an example of a high-voltage connection for an RE-DM4 controller.
Each AMX Lighting module has its high-voltage connectors marked on its circuit board.
Line, load, and neutrals are also clearly marked.
Connecting High-Voltage, Single-Phase Input Power and Loads
Follow these steps to wire high-voltage (120 VAC and 240 VAC), single-phase power connections (FIG. 16) to
any of the AMX Lighting modules.
1. Connect the green ground wire(s) to the copper ground lug on the enclosure. Ensure the ground wire is
properly connected to earth ground.
2. Connect the white neutral wire(s) to a terminal on the enclosure's neutral terminal block. Each terminal
on the block can accept two 10 AWG wires.
3. Provide a separate neutral wire for each dimmed zone.
4. Connect the black line input from the electrical devices to the module's line terminal. The line input
terminal accepts a 10 AWG copper conductor.
5. Connect load lines from the electrical devices to the Load terminals. Load 1 applies to dimmer 1, Load 2
applies to dimmer 2, and so on.
FIG. 15 High-voltage connections for an RE-DM4
Neutral
Line in
Load
Load
All high-voltage connections must comply with Class 1 wiring codes.
FIG. 16 RE-DM4 and RE-DM6 (as examples only) high-voltage, single-phase power connections for line input (hot),
neutral, and ground.
to Enclosure
ground terminal
Ground (green)
Hot (black) Neutral (white)
Ground (green)
Hot (black) Neutral (white)