NodeBuilder Errors Guide 6-7
NEX# Description
51
The device's clock rate (encoded value <id>) and the
transceiver's communication rate (encoded value <id>)
result in an invalid communication clock divider value. One
of the two input rates must be invalid [NEX#51]
The device's clock rate and the transceiver's communication rate
result in an invalid communication clock divider value. One of the
two input rates must be invalid. See error message for failure
details. Try increasing or lowering the Neuron clock speed. Contact
LonSupport if problem persists.
52
The transceiver requires a minimum clockrate which is
higher than the device's configured input clock speed
[NEX#52]
The transceiver requires a minimum clock-rate that is higher than
the device's configured input clock speed. This combination cannot
be used, you must choose a higher clock rate or a different
transceiver.
53
The encoded value for the device's clock input of <id> is not
within the supported range of <min> to <max> [NEX#53]
The encoded value for the device's clock input is not within the
supported range. See error message for failure details.
54
The encoded value for the channel's minimum clock rate of
<id> is not within the supported range of <min> to <max>
[NEX#54]
The encoded value for the channel's minimum clock rate of <id> is
not within the supported range. See error message for failure
details. Make sure your standard transceiver database
(stdxcvr.xml) has not been corrupted. An update might be
available at the www.lonmark.org website. Contact LonSupport if
problem persists.
55
Unable to determine preamble length using transceiver
<xcvr> [NEX#55]
Unable to determine the preamble length. See error message for
failure details. Make sure your standard transceiver database
(stdxcvr.xml) has not been corrupted. An update might be
available at the www.lonmark.org website. Contact LonSupport if
problem persists.
56
Unable to determine packet cycle duration using transceiver
<xcvr> [NEX#56]
Unable to determine the packet cycle duration. See error message
for failure details. Make sure your standard transceiver database
(stdxcvr.xml) has not been corrupted. An update might be
available at the www.lonmark.org website. Contact LonSupport if
problem persists.