APPENDIX A - Version Specific Software Documentation
05928 Rev F.0B A-35
DCN 5063 PRINTED DOCUMENTS ARE UNCONTROLLED
APPENDIX A-6: Terminal Command Designators, Revision F.0B
Table A-7: Terminal Command Designators, Revision F.0B
COMMAND A DDITIONAL COMMAND SYNTAX DESCRIPTION
? [ID] Display help screen and this list of commands
LOGON [ID] Password Establish connection to instrument
LOGOFF [ID] Terminate connection to instrument
SET ALL|name|hexmask Display test(s)
LIST [ALL|name|hexmask] [NAMES|HEX] Print test(s) to screen
Name Print single test
T [ID]
CLEAR ALL|name|hexmask Disable test(s)
SET ALL|name|hexmask Display warning(s)
LIST [ALL|name|hexmask] [NAMES|HEX] Print warning(s)
name Clear single warning
W [ID]
CLEAR ALL|name|hexmask Clear warning(s)
ZERO|LOWSPAN|SPAN [1|2] Enter calibration mode
ASEQ number Execute automatic sequence
COMPUTE ZERO|SPAN Compute new slope/offset
EXIT Exit calibration mode
C [ID]
ABORT Abort calibration sequence
LIST Print all I/O signals
name[=value] Examine or set I/O signal
LIST NAMES Print names of all diagnostic tests
ENTER name Execute diagnostic test
EXIT Exit diagnostic test
RESET [DATA] [CONFIG] [exitcode] Reset instrument
PRINT ["name"] [SCRIPT] Print iDAS configuration
RECORDS ["name"] Print number of iDAS records
REPORT ["name"] [RECORDS=number]
[FROM=<start date>][TO=<end
date>][VERBOSE|COMPACT|HEX] (Print DAS
records)(date format: MM/DD/YYYY(or YY)
[HH:MM:SS]
Print iDAS records
D [ID]
CANCEL Halt printing iDAS records
LIST Print setup variables
name[=value [warn_low [warn_high]]] Modify variable
name="value" Modify enumerated variable
CONFIG Print instrument configuration
MAINT ON|OFF Enter/exit maintenance mode
V [ID]
MODE Print current instrument mode
DASBEGIN [<data channel definitions>]
DASEND
Upload iDAS configuration
CHANNELBEGIN propertylist CHANNELEND Upload single iDAS channel
CHANNELDELETE ["name"] Delete iDAS channels