RE-DM4 and RE-DM6 RADIA Eclipse Dimmer Modules
Caution: Pre-Installation Notes
All Class 1 and 2 wiring must be connected to their dedicated terminals.
Class 1 wiring should be connected through the top of the enclosure, and Class 2 wiring through the
bottom.
Load conductors must be same size as line conductors, regardless of connected load.
Disconnect power while installing or connecting the unit.
Keep top and bottom air vents clear at all times, and maintain 12” (30.48 cm) clearance around the
top and bottom.
Test loads for shorts before connecting.
Class 2 wiring must be rated 300V or higher.
For indoor use only.
AC lighting loads only.
Line-In Connections
Using two feeds for Line 1 and Line 2 provides two 2400 W inputs.
Jumping Line 1 and Line 2 provides a single 2400 W input (FIG. 7)
This unit should be installed only by qualified electrical personnel, and in compliance
with all national electrical codes, local codes and ordinances.
To prevent possible personal injury or death, disconnect power to the enclosure at
the breaker box before attempting to work with any AMX Lighting modules.
To prevent possible personal injury or death, disconnect power to the enclosure at
the breaker box before attempting to install any AMX Lighting modules.
FIG. 7 Line-In Connections for the RE-DM6
Dual 2400 W Inputs without jumper
Single 2400 W Input with jumper